  • #five

considering of he powerfull pumps in todays washers, try and become that p trap as shut to the floor as possible. your stand piping needs to be as tall as you tin get it.

if it was me, sit that trap on the floor and make the stand pipage 24" tall

frodo

frodo

Only telephone call me Macgyver
  • #7

information technology can sit on the floor, you just dont want to have information technology and then high that your stand up piping is short.

the shorter the sand pipe, the more probable y'all will become suds backing out the height. at a later date

the minimum you are looking at,in the drawing, is the trap arm, non the trap. the trap goes down from the trap arm

answer your question, there is no lawmaking concerns [that i know of] confronting trap on the floor.

frodo

frodo

Just telephone call me Macgyver
  • #9

max stand pipe height is 24" upc code. i have no idea what it is IPC,

frodo

frodo

Just telephone call me Macgyver
  • #11

42? is that all p-trap stand pipe length's. like a trap under a fd can exist 42" down?

frodo

frodo

Just telephone call me Macgyver
  • #13

but, the 24" code is for fixtures, correct?
a washer or washer box is a fixture. and so would non the 24" dominion apply to the stand pipe for that fixture?

that has e'er been my understanding. but hey,,,teach this old domestic dog new tricks

this is upc..not ipc 1001.3 and 1001-4. i know ipc let you do any damn matter! lol

scan0007.jpg

Last edited:

  • #14

Establish this in Louisiana plumbing code:
I. Distance of Trap Weir from Fixture Outlet. The
vertical distance from the fixture outlet to the trap weir, or
from the outlet of an integrally trapped h2o closet or
similar fixture to the horizontal piping connecting the fixture
to its vent, shall not exceed 24 inches (610 mm).
1. Exception. Washing Machine Pumped Waste Bleed.
The vertical distance from the vertical standpipe inlet
receiving the pumped waste belch from a washing
machine (laundry) to the trap weir shall be a minimum of xxx
inches (762 mm) and a maximum of 48 inches (1219 mm),
with the vertical standpipe inlet terminating a minimum of
34 inches (864 mm) above finished floor or in accord
with the manufacturer's recommendation.

AUTHORITY NOTE: Promulgated in accordance with R.S.
40:four(A)(7) and R.S. twoscore:5(2)(3)(7)(9)(16)(17)(twenty).
HISTORICAL Note: Promulgated past the Department of
Health and Hospitals, Office of Public Wellness, LR 38:2867
(November 2022).

Granted, that might not apply to other states. I think Louisiana code is based on IPC.

Editing to remove my annotate nearly cleanouts since I mis-read something. From my agreement a cleanout is required for the pipe afterwards the trap, but not in the trap or before?

Concluding edited:

frodo

frodo

Just call me Macgyver
  • #19

is that ipc? so the trap arm in ipc code for a WC tin be as long as you lot need it? jeeeeeez..can you lot say gurgle??